Fixed Combustible Gas Detector
Fixed LPG Gas Leak Detector Combustible Gas Detector with Explosion-Proof Alarm lamp
Overview
The fixed gas detector is an advanced industrial safety device designed to monitor gas concentrations in hazardous environments. It employs high-quality catalytic or electrochemical sensors (from leading brands) to accurately detect flammable or toxic gases and convert the gas density into a standard 4–20mA analog signal or digital output (RS485) for integration with control systems.
Key Applications
Widely used in refineries, chemical plants, LPG stations, boiler rooms, painting facilities, petroleum, metallurgy, pharmaceuticals, gas transportation, and wastewater treatment plants—anywhere gas leaks pose a risk.
Detect Gas: O2, Combustible Gas, CO, H2S, NH3, H2, Cl2, HCl, SO2, NO, NO2, CO2, C2H4O, C2H6O, CH3OH/ CH4O, HCHO/ CH2O, HCOOH, C2H3Cl, C4H8, VOC, O3, PH3, HCN.
Core Features
- High-Performance Sensing
- Electrochemical/catalytic sensors with high sensitivity, anti-interference capability, and long lifespan.
- Calibrated via multi-stage standard gas and compensation algorithms for precision and stability.
- Robust Design
- Explosion-proof (Ex d IIC T6 Gb) and IP65-rated enclosure for harsh/outdoor environments.
- Wall-mounted waterproof housing for easy installation.
- Flexible Outputs & Compatibility
- 4–20mA current signal (compatible with most alarm controllers/DCS systems).
- Optional RS485 digital output and relay contacts for alarms/exhaust systems.
- User-Friendly Operation
- Large LCD/LED display for real-time, on-site readings.
- Infrared remote control for parameter adjustment (no disassembly needed).
- Password-protected keypad to prevent accidental tampering.
- Smart Alerts & Maintenance
- Two-stage alarms (local + relay-triggered external alarms/ventilation).
- Self-diagnosis for sensor faults with error signals.
- Hot-swappable sensors for quick replacement without downtime.
- Customization
- Supports multiple gas types and customizable detection ranges.
- 10–30V DC wide-voltage input for versatile power supply compatibility.
SPECIFICATIONS
Detect gas | Detectrange | Resolution | L-alarm | H-alarm |
CH4 | 0-100%LEL | 1%LEL | 20%LEL | 50%LEL |
LPG | 0-100%LEL | 1%LEL | 20%LEL | 50%LEL |
EX | 0-100%LEL | 1%LEL | 20%LEL | 50%LEL |
C3H8 | 0-100%LEL | 1%LEL | 20%LEL | 50%LEL |
C2H6O | 0-100%LEL | 1%LEL | 20%LEL | 50%LEL |
CO | 0-1000PPM/0-100PPM | 1PPM | 200PPM/20PPM | 500PPM/50PPM |
H2S | 0-100PPM | 1PPM | 20PPM | 50PPM |
H2 | 0-1000PPM | 1PPM | 200PPM | 500PPM |
NH3 | 0-100PPM/0-1000PPM | 1PPM | 20PPM/200PPM | 50PPM/500PPM |
O2 | 0-30%VOL | 0.1%VOL | lower 19%VOL | 23%VOL |
HCL | 0-100PPM | 1PPM | 20PPM | 50PPM |
CO2 | 0-5000PPM/0-50000PPM | 1PPM | 1000PPM | 2500PPM |
C2H4 | 0-100PPM | 1PPM | 20PPM | 50PPM |
C2H2 | 0-100PPM | 1PPM | 20PPM | 50PPM |
CL2 | 0-100PPM | 1PPM | 20PPM | 50PPM |
O3 | 0-100PPM/0-10PPM/0-5PPM | 1PPM | 20PPM | 50PPM |
SO2 | 0-100PPM | 1PPM | 20PPM | 50PPM |
HCN | 0-100PPM | 1PPM | 20PPM | 50PPM |
HF | 0-10PPM | 0.1PPM | 20PPM | 50PPM |
PH3 | 0-100PPM | 1PPM | 20PPM | 50PPM |
NO | 0-100PPM | 1PPM | 20PPM | 50PPM |
NO2 | 0-100PPM | 1PPM | 20PPM | 50PPM |
ETO | 0-100PPM | 1PPM | 20PPM | 50PPM |
CLO2 | 0-100PPM | 1PPM | 20PPM | 50PPM |
C2H3CL | 0-100PPM | 1PPM | 20PPM | 50PPM |
CH2O | 0-100PPM | 1PPM | 20PPM | 50PPM |
PID | 0-100PPM(customizable) | 1PPM | 20PPM | 50PPM |
Note:
1. The detection ranges listed are all conventional. If you need a special range, you can contact us for customization. 2. The alarm value can be set. |